Onduleur Superwatt régime TT du neutre pas aux normes en mode autonome / Off Grid

Description of the floating neutral phenomenon when some inverters go into autonomous mode.

**** Beware, electricity is dangerous because it is invisible, silent and odorless.

The consequences can be fatal if you do not master this subject ****

The neutral is no longer grounded, so it is in floating mode. 110V on the blue and 120V on the phase.
This would not be a problem if it did not put your electrical box out of play and especially the differentials that can no longer detect a leakage current and therefore break.
I do not understand how these inverters can be sold in France ?

Explanatory video below

[yotuwp type= »videos » id= »z6DRaXrBN1M » ]

2 réponses sur “Onduleur Superwatt régime TT du neutre pas aux normes en mode autonome / Off Grid”

  1. salut, j’ai eu le meme problème et je l’ai résolu en shuntant la sortie AC neutre et la terre, avec une résistance de 1KOHM a 0.01€, cordialement

    1. Ça je n’aurais pas osé. Mais si ça fonctionne, il n’y a pas de raison de ne pas le partager. En effet, solution à 0€, radicale.
      On ne voit pas trop bien la résistance et ses connexions. Pourrais-tu en poster une plus grande et bonne définition ?
      Question, as-tu mis un testeur de phases pour vérification ainsi que de tester un courant de fuite pour voir si ton tableau électrique détecte bien la fuite de courant ?
      Ce serait cool.

Laisser un commentaire